Test every device at a site. In the app, results save to your company and roll up into Compliance.
Sample site - the annual inspection is under way. Tap Pass or Fail on any device. Start a free trial and your results are waiting to save to your account.
1200 Lincoln Ave · Last inspection Nov 3, 2025
Devices
16
Tested this visit
4
Failed
1
Due or never tested
12
One record per NFPA 72 task, pass only if every device passed.
Deficiencies (1)
SD-002 (Classroom 102) - Initiating devices - functional test (smoke, heat, manual): No alarm at panel - head dirty, replace and retest · Oct 9, 2026
Add a device
FACP-001
Fire Alarm Control Panel · Fire Alarm · Main electrical room
Control unit & trouble signals - inspect and test
Current · due Oct 9, 2027
Every 12 months · NFPA 72 14.4.3.2 item 2 · last Pass Oct 9, 2026
How to test
Check lamps/LEDs and display, fuses, primary power and trouble signals; test ground fault and open-circuit supervision.
Recorded Pass this visit
History
Nov 3, 2025 · Control unit & trouble signals - inspect and test · Pass
Oct 9, 2026 · Control unit & trouble signals - inspect and test · Pass
ANN-001
Annunciator · Fire Alarm · Main entrance lobby
Control unit & trouble signals - inspect and test
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 2 · last Pass Nov 3, 2025
How to test
Confirm the annunciator shows alarm, supervisory and trouble signals and its lamp/LCD test works.
History
Nov 3, 2025 · Control unit & trouble signals - inspect and test · Pass
PS-001
Pull Station · Fire Alarm · Main entrance
Initiating devices - functional test (smoke, heat, manual)
Current · due Oct 9, 2027
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Pass Oct 9, 2026
How to test
Operate the station mechanically; confirm the alarm at the panel; reset with the key or tool.
Recorded Pass this visit
History
Nov 3, 2025 · Initiating devices - functional test (smoke, heat, manual) · Pass
Oct 9, 2026 · Initiating devices - functional test (smoke, heat, manual) · Pass
PS-002
Pull Station · Fire Alarm · East stair, 1st floor
Initiating devices - functional test (smoke, heat, manual)
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Pass Nov 3, 2025
How to test
Operate the station mechanically; confirm the alarm at the panel; reset with the key or tool.
History
Nov 3, 2025 · Initiating devices - functional test (smoke, heat, manual) · Pass
SD-001
Smoke Detector · Fire Alarm · Corridor A by room 101
Initiating devices - functional test (smoke, heat, manual)
Current · due Oct 9, 2027
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Pass Oct 9, 2026
How to test
Functional test with listed smoke or aerosol per the manufacturer; confirm the alarm at the panel with the right address/zone.
Recorded Pass this visit
Smoke detector sensitivity test
Current · due May 7, 2027
Every 24 months · NFPA 72 14.4.4.3 · last Pass May 7, 2025
How to test
Sensitivity test by a listed method or the panel's sensitivity report - first within 1 year of install, then every 2 years.
History
Nov 3, 2025 · Initiating devices - functional test (smoke, heat, manual) · Pass
May 7, 2025 · Smoke detector sensitivity test · Pass
Oct 9, 2026 · Initiating devices - functional test (smoke, heat, manual) · Pass
SD-002
Smoke Detector · Fire Alarm · Classroom 102
Initiating devices - functional test (smoke, heat, manual)
Failed
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Fail Oct 9, 2026
How to test
Functional test with listed smoke or aerosol per the manufacturer; confirm the alarm at the panel with the right address/zone.
Recorded Fail this visit
Smoke detector sensitivity test
Current · due May 7, 2027
Every 24 months · NFPA 72 14.4.4.3 · last Pass May 7, 2025
How to test
Sensitivity test by a listed method or the panel's sensitivity report - first within 1 year of install, then every 2 years.
History
Nov 3, 2025 · Initiating devices - functional test (smoke, heat, manual) · Pass
May 7, 2025 · Smoke detector sensitivity test · Pass
Oct 9, 2026 · Initiating devices - functional test (smoke, heat, manual) · Fail - No alarm at panel - head dirty, replace and retest
SD-003
Smoke Detector · Fire Alarm · Library
Initiating devices - functional test (smoke, heat, manual)
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Pass Nov 3, 2025
How to test
Functional test with listed smoke or aerosol per the manufacturer; confirm the alarm at the panel with the right address/zone.
Smoke detector sensitivity test
Current · due May 7, 2027
Every 24 months · NFPA 72 14.4.4.3 · last Pass May 7, 2025
How to test
Sensitivity test by a listed method or the panel's sensitivity report - first within 1 year of install, then every 2 years.
History
Nov 3, 2025 · Initiating devices - functional test (smoke, heat, manual) · Pass
May 7, 2025 · Smoke detector sensitivity test · Pass
SD-004
Smoke Detector · Fire Alarm · Corridor B by room 201
Initiating devices - functional test (smoke, heat, manual)
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Pass Nov 3, 2025
How to test
Functional test with listed smoke or aerosol per the manufacturer; confirm the alarm at the panel with the right address/zone.
Smoke detector sensitivity test
Current · due May 7, 2027
Every 24 months · NFPA 72 14.4.4.3 · last Pass May 7, 2025
How to test
Sensitivity test by a listed method or the panel's sensitivity report - first within 1 year of install, then every 2 years.
History
Nov 3, 2025 · Initiating devices - functional test (smoke, heat, manual) · Pass
May 7, 2025 · Smoke detector sensitivity test · Pass
HD-001
Heat Detector · Fire Alarm · Kitchen
Initiating devices - functional test (smoke, heat, manual)
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Pass Nov 3, 2025
How to test
Restorable: listed heat source per the manufacturer. Non-restorable (fusible): mechanical or electrical test - never apply heat.
History
Nov 3, 2025 · Initiating devices - functional test (smoke, heat, manual) · Pass
DD-001
Duct Detector · Fire Alarm · AHU-1 return duct
Duct smoke detectors - functional test
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 14 · last Pass Nov 3, 2025
How to test
Test through the test port or remote test station per the manufacturer; confirm fan shutdown and check the air pressure differential.
History
Nov 3, 2025 · Duct smoke detectors - functional test · Pass
HS-001
Horn/Strobe · Fire Alarm · Corridor A
Notification appliances - audible and visible test
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 17 · last Pass Nov 3, 2025
How to test
Activate the circuit; confirm the horn sounds temporal-3 and the strobe flashes in sync; setting (candela/dB) matches the plan.
History
Nov 3, 2025 · Notification appliances - audible and visible test · Pass
HS-002
Horn/Strobe · Fire Alarm · Gym
Notification appliances - audible and visible test
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 17 · last Pass Nov 3, 2025
How to test
Activate the circuit; confirm the horn sounds temporal-3 and the strobe flashes in sync; setting (candela/dB) matches the plan.
History
Nov 3, 2025 · Notification appliances - audible and visible test · Pass
HS-003
Horn/Strobe · Fire Alarm · Cafeteria
Notification appliances - audible and visible test
Due soon · due Nov 3, 2026
Every 12 months · NFPA 72 14.4.3.2 item 17 · last Pass Nov 3, 2025
How to test
Activate the circuit; confirm the horn sounds temporal-3 and the strobe flashes in sync; setting (candela/dB) matches the plan.
History
Nov 3, 2025 · Notification appliances - audible and visible test · Pass
WF-001
Waterflow Switch · Fire Alarm · Sprinkler riser room
Waterflow alarm devices
Due soon · due Nov 2, 2026
Every 6 months · NFPA 72 14.4.3.2 item 14 · last Pass May 2, 2026
How to test
Flow water through the inspector's test connection; alarm within 90 seconds; confirm the retard setting.
History
May 2, 2026 · Waterflow alarm devices · Pass
TS-001
Tamper Switch · Fire Alarm · Riser OS&Y valve
Supervisory devices (valve tamper, low air)
Due soon · due Nov 2, 2026
Every 6 months · NFPA 72 14.4.3.2 item 14 · last Pass May 2, 2026
How to test
Operate the valve; supervisory signal within 2 turns of the handwheel (or 1/5 of travel); restores only when fully open.