Fire Alarm
Manual Pull Station
Also called: pull box, manual station, MPS, fire alarm box
A person pulls the handle to start the alarm. Conventional stations close a dry contact on an initiating circuit; addressable stations have a built-in module and report their own address on the SLC.
Wiring schematic
- + / signal
- − / common
- Power / contacts
- Data / network
- 120 VAC
- Audio / beam
Conventional: the N.O. contact closes the IDC (EOL resistor at the last device). Addressable: the station's built-in module sits on the SLC like any other device - no EOL.
Typical specs
| Action | Single action (pull) or dual action (push, then pull) |
|---|---|
| Contact | N.O. dry contact (conventional) or built-in addressable module |
| Reset | Key or hex/Allen tool |
| Back box | Single-gang, double-gang or surface box (per model) |
| Listing | UL 38 |
Install & code notes
- Operable handle 42-48 in above the floor (NFPA 72).
- Within 5 ft of the entrance to each exit on every floor.
- No more than 200 ft travel distance to a station on the same floor.
- Add stations so a wide group opening (over 40 ft) has one on each side.
- Protective covers (e.g. STI Stopper) are allowed where stations get false-pulled; the cover must not block operation.
Common models
| Maker | Model | Notes | Datasheet |
|---|---|---|---|
| Notifier | NBG-12LX | Addressable, dual action, FlashScan/CLIP | Find ↗ |
| Fire-Lite | BG-12LX | Addressable, for Fire-Lite addressable panels | Find ↗ |
| Fire-Lite | BG-12 | Conventional, N.O. contact | Find ↗ |