The numbers every fire alarm submittal needs: voltage drop on each notification appliance circuit, the standby battery, the strobe candela for each room and how many detectors a room takes. Each result shows the formula and the NFPA 72 section behind it.
NAC voltage drop
Will the last horn strobe on a notification appliance circuit get enough voltage at the end of battery life?
Strobes and horn strobes on the circuit, by candela
18.66 V at the last appliance
1.74 V drop (8.5%) carrying 1.42 A over 200 ft.
✓ At or above 16 V: this circuit works.
✓ 1.42 A is 71% of the 2 A circuit rating.
Longest run on 14 AWG with this load: 506 ft.
Smallest wire that works: 16 AWG.
Drop = current × 2 × one-way length × ohms per foot (NEC Chapter 9, Table 8). Spread evenly, n appliances see (n + 1) ÷ 2n of that. Strobe currents are typical values at 24 V; use the data sheet's figure at the candela you set.
Standby battery size
Amp-hours for 24 hours of standby and then the alarm, for a panel or a NAC power supply.
Fire alarm control panel
Addressable smoke detector
Monitor module / pull station
Horn strobe 75 cd
The currents filled in are typical starting points. Replace them with the numbers on your data sheets.
Use 7 Ah batteries
Needs 6.26 Ah: 0.208 A × 24 h standby (4.99 Ah) + 2.659 A alarm (0.22 Ah), plus 20%.
Ah = (standby A × 24 h + alarm A × alarm time) × (1 + margin). NFPA 72: 24 hours of standby, then 5 minutes of alarm, or 15 minutes for emergency voice/alarm communications. A 24 V system uses two 12 V batteries in series; the Ah rating is per battery. Make sure the charger is listed for that size. Appliances on a NAC power supply with its own batteries count against that supply, not the panel.
Strobe candela
The candela setting for a room's wall strobe, or how many strobes a corridor needs.
1 wall strobe at 75 cd
A 40 ft room needs at least 60 cd; 75 cd is the next common setting.
NFPA 72 Table 18.5.5.4.1(a), one wall-mounted strobe per room, by the larger side: 20 ft → 15 cd, 28 → 30, 30 → 34, 40 → 60, 45 → 75, 50 → 94, 54 → 110, 55 → 115, 60 → 135, 63 → 150, 68 → 177, 70 → 184. Mount 80 to 96 in. above the floor. Corridors 20 ft wide or less (18.5.5.5): 15 cd, within 15 ft of each end, no more than 100 ft apart.
Detector count and spacing
How many spot smoke or heat detectors a room with a smooth, flat ceiling needs, and where they go.
4 smoke detectors
2 along × 2 across: 30 ft apart along the length and 20 ft across, the first ones 15 ft and 10 ft from the walls.
Farthest ceiling point from a detector: 18 ft (keep it within about 0.7 × the spacing, 21 ft).
Smoke: 30 ft nominal spacing on smooth ceilings (NFPA 72 17.7.4.2.3), half that to the walls, every point within 0.7 × spacing. Heat: the listed spacing, reduced for ceilings over 10 ft (Table 17.6.3.5.1: 12 ft × 0.91, 14 ft × 0.84, 16 ft × 0.77, 20 ft × 0.64, 30 ft × 0.34). Beams, joists, sloped ceilings and strong air movement change the layout.
These do the arithmetic; they don't replace the code. They follow NFPA 72 (2022) for smooth, flat ceilings and typical device currents. The edition your AHJ enforces, the manufacturers' data sheets and installation instructions, the engineer of record and the AHJ have the final say.
How to use them on a job
Notification circuits. Count the strobes and horn strobes on each NAC by candela setting, or type the total current from the data sheets, then the wire size and the one-way length to the last appliance. The calculator starts at 20.4 V (85% of 24 V, the battery near the end of standby) and checks that the last appliance still gets at least 16 V. It also gives the longest run that works and the smallest wire that would. Read more in the NAC voltage drop guide.
Batteries. List the panel and every device it powers with its standby and alarm current. The calculator adds 24 hours of standby to 5 minutes of alarm (15 for emergency voice/alarm), adds your safety margin and picks the next common battery size. Do the same for each NAC power supply that carries its own batteries.
Strobes and detectors. Enter a room's size for the wall strobe's candela from NFPA 72's one-strobe table, or a corridor's length for the number of 15 cd strobes. For detectors, enter the room and ceiling height: smoke detectors go on a 30 ft grid, heat detectors on their listed spacing reduced for high ceilings. See the smoke detector spacing guide for the 0.7 × S rule.
These calculators do the arithmetic; they don't replace the code. They cover smooth, flat ceilings and use typical device currents. The edition your AHJ enforces, the manufacturers' data sheets and the AHJ have the final say.